Who among us tracks the accuracy of Manual J?

Who among us tracks the accuracy of Manual J?

I have hour meters on maybe 20 systems now.    I like to see the run time when it's "4" degrees in Kansas City.  99% rate in KC is +4' degrees.  My goal at 4' is 100% run time.   I have a super sealed home 2,100 square feet  with a 2 ton ground type heat pump R-30 walls, R-60 attic, R-8 windows & doors with 98% run time @ "+ 4' ".  When the strip heat turned on, it smelled up the home with the dirt  off the 5 KW strip, heat burned off the dust.   If you fine tune ACCA MJ  with a blower door number and infrared camera  you can get closer.   If  I find a real drafty building - I am more off.   Or building owner just turn up the heat more.  

4/5 of heat loss is at night. The wind tends to die mid-night and MJ tends to keep the wind up.  If you just run the number with Manual J I tend to get larger system sizes than needed - do not add more fudge factor. 

Views: 219

Comment

You need to be a member of Home Energy Pros Forum to add comments!

Join Home Energy Pros Forum

Comment by Eric Kjelshus on March 7, 2016 at 6:53pm

Most of the Thermostat controls I use Look at RH - humidity also  but still its just longer run time.   I am mixed very humid to dry and cold.   I have been using outside air with a damper to outside to make the building positive.  Could the outside air make 20% -30% higher fan use and higher power use?

Comment by John Proctor on March 7, 2016 at 11:25am

Eric  It is doubtful that the fan motor is using more energy, the electrical use of PSC motors is nearly constant regardless of speed. What climate are you referring to? If it is a wet climate, then you need the latent removal and should go back to 350 CFM per ton. However the lack of latent capacity should not increase the electrical usage since the thermostat controls only to temperature, not humidity.

If the duct system is not restrictive, an ECM/BPM motor would deliver the right airflow at a lower watt draw.

Comment by Eric Kjelshus on March 6, 2016 at 2:11pm

Do you see the new AC with low sensible and very large coils needing more run time?  That last 2 ton this year was just 91% Sensible and 9% Latent.   the one I took out a AC built in 1990 was 70%/30% with very small very cold coil but 350 CFM/ton now razing the CFM to 400 per ton and not the Latent removal.   I am seeing power bill go up with higher run time and more power to run the fan?   Older air handler had drives with smaller motors.   

Comment by John Proctor on March 3, 2016 at 11:06am

Proctor Engineering has done many studies on Manual J vs. true load. The short answer is the sensible load is actually 2/3 of the Manual J 7 (note 7) estimated sensible load and Manual J8 calculates an even higher sensible load. The latent load estimate varies compared to the actual latent loads. Sometimes it is too high (a tight house in a wet climate). Sometimes it is too low ( a leaky house in a wet climate).

There is a Home Energy article on all this on their website or here:

http://www.proctoreng.com/dnld/Home_Energy_Sizing_AC.pdf

Here is a letter from Trane opposing the acceptance of Manual J 8.

http://www.proctoreng.com/dnld/ACCA.pdf

Forum Discussions

Efficiency of furnace

Started by Jignesh in General Forum. Last reply by Barbara Smith yesterday. 7 Replies

Best brands for furnace

Started by Jignesh in General Forum. Last reply by Barbara Smith yesterday. 1 Reply

Insulation Blower Recommendations?

Started by Jim Conlon in General Forum. Last reply by Cameron Home Insulation on Monday. 2 Replies

2005 EPAct tax credit

Started by Mandy Leazenby in General Forum. Last reply by Sean Lintow Sr on Thursday. 3 Replies

Latest Activity

Profile IconM Johnson and Jerry Phillips joined Home Energy Pros Forum
2 hours ago
Sara Watson posted a blog post

6 Tips to Pick Out The Best Solar Outdoor Lights

You have a beautiful home in Florida and plan to add a little sparkle to your front garden, patio,…See More
19 hours ago
DesignTech liked DesignTech's photo
21 hours ago
Anthony Roy is now a member of Home Energy Pros Forum
yesterday
Barbara Smith commented on Barbara Smith's video
yesterday
Barbara Smith replied to Jignesh's discussion Efficiency of furnace
"Installation and proper sizing is important to getting the best performance out of your furnace.…"
yesterday
Barbara Smith replied to Jignesh's discussion Best brands for furnace
"Check ENERGY STAR and Consumer Reports.…"
yesterday
Barbara Smith replied to Diane Chojnowski's discussion Support Mike Rogers, a long-time home performance hero, as he battles sinus cancer. in the group News & Announcements
yesterday
Barbara Smith joined Diane Chojnowski's group
Thumbnail

News & Announcements

Share your news and announcements with the community in this group.To post news or an announcement,…See More
yesterday
Diane Chojnowski added a discussion to the group News & Announcements
Thumbnail

Support Mike Rogers, a long-time home performance hero, as he battles sinus cancer.

Support Mike Rogers, a long-time home performance hero, as he battles sinus cancer. Write a note, a…See More
yesterday
Eric Kjelshus replied to Jignesh's discussion Efficiency of furnace
"I like looking at system efficiency - Lets say the you have a 95% gas using furnace 100,000…"
Monday
Cameron Home Insulation replied to Jim Conlon's discussion Insulation Blower Recommendations?
"Hi, Rent a Cellulose Insulation Blower from your local Home Depot. Get more information about…"
Monday
Todd Abercrombie liked Barbara Smith's video
Saturday
Jim Hensen replied to Jignesh's discussion Efficiency of furnace
"Great question - what the efficiency rating means is one of the most common questions we we asked.…"
Saturday
Michael Schettine's blog post was featured

Framing production combined with air sealing

Building Tighter Homes with Gasketed FramingIf you follow our blog, you know that we talk quite a…See More
Friday
Profile IconMichael E and Jason Dion joined Home Energy Pros Forum
Friday
Jason Dion joined Sean Lintow Sr's group
Thumbnail

Best Practices (Residential)

Best Building, Retrofitting, or even Auditing Practices - what are they, what should change, what…See More
Friday
Jason Dion joined Michael Stuart's group
Thumbnail

INFRARED THERMOGRAPHY USERS

This group is dedicated to knowledge sharing and discussion of infrared thermography for building…See More
Friday
Jason Dion joined allen p tanner's group
Thumbnail

Energy Auditing Equipment for Sale, Trade or to Purchase

Discuss the pros and cons of the equipment you are interested in prior to purchase. Post equipment…See More
Friday
Jason Dion joined Allison A. Bailes III's group
Thumbnail

HVAC

HVAC design, Manuals J, S, T, & D, Duct leakage, Air flow, ENERGY STAR new home requirements,…See More
Friday

Photos

  • Add Photos
  • View All

© 2018   Created by Home Performance Coalition (HPC)   Powered by

Badges  |  Report an Issue  |  Terms of Service