Or is there? This saying is an old adage in our industry to let the technician know that the refirgerant charge is "all set". You see, there must be a steady stream of liquid to the metering device for it to function properly. For sake of conversation, let's use the TXV. In order for most TXV's to throttle and correctly maintain the desired Superheat, there must be a minimum of 2F of subcooled liquid at the valve (not where it is measured, near the condenser). If the liquid were to flash off ahead of the valve, destruction to the TXV may occur. So, some old timer along the way figured he would look into the sight glass (what we install in residential air-conditioners this day and age are moisture indicators), and determine if there was a steady stream of liquid, or in other words: "No Bubble, No Troubles!". For years, this method combined with "beer can cold", or "sweating back to the compressor" were used to determine the refrigerant charge was 'close enough'. Those that know me know that I speak from experience here, I have tried them all!
What we were missing was the fact we were overcharging systems, significantly. Sometimes to the point of slugging compressors, particularly with fixed orifice systems. Having a steady stream of liquid does not mean the refrigerant charge is correct! I know, I am preaching to the choir here. You see, if you are reading my blog than you care enough to learn how to do things right. I am sure you have picked up an installation manual recently and actually flipped through it, instead of kneeling on it and tossing it into the trash! If you have, you will notice that no where in these books does it read, "No Bubbles, No troubles!" If it were that simple, than they would have put it into the start-up procedure. Do me a favor: stop wasting energy and killing compressors, okay? Take the extra ten minutes to measure the Superheat and Subcooling on the system, and verify they are within manufacturer specs. Believe me, you will have less warrantied labor work where you make zero profit replacing compressors!

http://excessair.blogspot.com/p/blog-page_23.html

Views: 162

Comment

You need to be a member of Home Energy Pros Forum to add comments!

Join Home Energy Pros Forum

Latest Activity

Dara Bowser replied to Don Fugler's discussion joining ducts in the group HVAC
"Good to hear you have clean dryer ducts Don. The dryer duct issues that we run into are…"
2 hours ago
Don Fugler replied to Don Fugler's discussion joining ducts in the group HVAC
"David, If the IMC mandates metal dryer duct and prohibits metal screws, they must be accepting…"
3 hours ago
David Butler replied to Don Fugler's discussion joining ducts in the group HVAC
"I never checked that before. Checking now... Section M1502.4.2 of the International Residential…"
3 hours ago
Joseph Frasier is now a member of Home Energy Pros Forum
3 hours ago
Don Fugler replied to Don Fugler's discussion joining ducts in the group HVAC
"Brendan, Thanks for that response. Because of your warning, I just went down to the basement and…"
7 hours ago
Brendan Reid replied to Don Fugler's discussion joining ducts in the group HVAC
"Hi Don, Summary: DRYER VENT: screws bad idea, possibly prohibited by code. METAL DUCT: must be…"
8 hours ago
Profile IconBrendan Reid and David Butler joined Allison A. Bailes III's group
Thumbnail

HVAC

HVAC design, Manuals J, S, T, & D, Duct leakage, Air flow, ENERGY STAR new home requirements,…See More
8 hours ago
Profile IconSean Wiens and David Butler joined Chris Laumer-Giddens's group
Thumbnail

Energy Efficient Design

Energy efficiency starts at the drafting table...How architects and designers can help buildings…See More
16 hours ago

Photos

  • Add Photos
  • View All

© 2017   Created by Home Performance Coalition (HPC)   Powered by

Badges  |  Report an Issue  |  Terms of Service