John Tooley said, “Air is like crooked rivers, crooked people, teenagers, and cheap labor.  It always seeks the path of least resistance.”  He didn’t say that Angry air is Noisy air.   Air doesn’t like being forced through corrugated, flexible ducting, pushed around corners, and made to force open dampers.  It resists being made to perform in a way that it doesn’t want to.  It takes more and more force as the resistance increases.  Air is just fine when you just let it move at will.  It can become amazingly strong as any building that has met a hurricane or tornado can attest to.  And as objects like asteroids and space capsules hurtle through the atmosphere they burn up!

ASHRAE 62.2 requires bathroom fans to make no more noise than a quiet refrigerator in a quiet kitchen: 1 sone or less.  And if you put an Energy Star bathroom fan on the bench and plug it in, you can barely hear it.  It’s amazingly quiet.  “Is it running?” people ask.  And it is.  So how come once you install the fan in the ceiling it gets uncomfortably loud?

Fan manufacturers not only made these fans quiet, they put DC motors in them that are extremely tolerant ofchanges in pressure.  As the pressure increases in the installation, the fan motor compensates by using more power to increase the speed of the spinning wheel that is pushing the air.  (Notice the curve on this graph that starts on on the left side and then drops off the cliff at about 75 cfm.  It has about the same airflow from 0.45 iwg as it does at 0.0 iwg!)  That’s a wonderful thing because people can install the fans horribly and step on the duct and lots of other nasty things and still come out with the same airflow . . . but not the same sound level.  What was really, really quiet is now uncomfortably loud.  And as houses get tighter they get quieter and a noisy fan is annoying which is why so much effort was made to get them quiet so they could run all the time without bothering anyone!

I have found that builders get aggravated because these quiet and expensive fans that they have been compelled to install really aren’t all that quiet.  And they should be quiet.  They have been designed to be quiet.  Tested to be quiet.  And if you disconnect them from the installation, they are quiet.

So here’s a simple way to determine if the fan is working right: listen to it.  If the air is angry, it will be noisy and noisy DC fans equal bad installation.  The air is yelling at you.  I have found ducts filled with the foam that was sprayed on the house for insulation.  Backdraft dampers remain taped closed.  Ducts terminated against a wall or floor in the attic and don’t actually get to the outside.  If a bathroom fan that is rated to be < 0.3 sones is noisy, its a bad installation.  Period.  Fix it.  It may still be moving enough air to meet the ventilation requirements, but if it is noisy the homeowner will find a way to turn it off and stuff it full of socks.  Then the air in the house will get bad and people will get sick.  And the occupants will get angrier than the air!  And the really dumb thing is that all these codes and standards and mathematical computations and formulas to size the fan correctly mean absolutely nothing if the fan is turned off.

Views: 146

Comment

You need to be a member of Home Energy Pros Forum to add comments!

Join Home Energy Pros Forum

Forum Discussions

Too many Heat Pump Water Heaters in a basement?

Started by Brad Cook in General Forum. Last reply by David Butler 23 hours ago. 9 Replies

How would you insulate this roof?

Started by David Butler in General Forum. Last reply by David Butler yesterday. 2 Replies

Dirty solar panels

Started by Evan Mills in General Forum. Last reply by Stacie Bagnasco yesterday. 1 Reply

Fixing a water heater?

Started by John Shillito in Best Practices. Last reply by Eric Kjelshus on Friday. 21 Replies

Latest Activity

Profile IconSarah Burger, Troy Spindler, Mike Berg and 3 more joined Home Energy Pros Forum
2 hours ago
David Butler replied to Brad Cook's discussion Too many Heat Pump Water Heaters in a basement?
"theoretically, let's say you perfectly isolate the HPWH from a heat source. The HPWH's…"
23 hours ago
David Butler replied to David Butler's discussion How would you insulate this roof?
"Interesting idea. Commercial roof on a slope! Typical density for roofing spray foam is 2.5 to 3.0…"
yesterday
Summer Redman added a discussion to the group Job Board
Thumbnail

Hiring 2 Training Specialists in Champaign-Urbana, Illinois

The Applied Research Institute (ARI) at the University of Illinois at Urbana-Champaign is seeking…See More
yesterday
Summer Redman joined Diane Chojnowski's group
Thumbnail

Job Board

This group is for posting jobs related to all aspects of the home performance industry including…See More
yesterday
Profile IconJeff Farlow, John Hatfield, Crystal McLain and 5 more joined Home Energy Pros Forum
yesterday
Stacie Bagnasco replied to Evan Mills's discussion Dirty solar panels
"This is a great idea. I clicked on your discussion because it made me remember that I forgot to get…"
yesterday
Kirsten Richnavsky posted an event
Thumbnail

rCloud - The Future of Testing at Your Office or Home

October 18, 2017 from 2pm to 3pm
Integrating rCloud as an essential part of your RESNET QA process.Retrotec’s rCloud app is here,…See More
yesterday

Photos

Loading…
  • Add Photos
  • View All

© 2017   Created by Home Performance Coalition (HPC)   Powered by

Badges  |  Report an Issue  |  Terms of Service